Description
Electrical data
Ratings per IEC/EN
Ratings per | IEC/EN 60947-7-1 |
Nominal voltage (III/3) | 500V |
Rated impulse voltage (III/3) | 6kV |
Rated current | 13.5A |
Rated current 2 | 16A |
Legend (ratings) | (III / 3) ≙ Overvoltage category III / Pollution degree 3 |
Ratings per UL
Approvals per | UL 1059 |
Rated voltage UL (Use Group B) | 300V |
Rated current UL (Use Group B) | 15A |
Rated voltage UL (Use Group C) | 300V |
Rated current UL (Use Group C) | 15A |
Ratings per CSA
Approvals per | CSA 22.2 No 158 |
Rated voltage CSA (Use Group B) | 600V |
Rated current CSA (Use Group B) | 10A |
Rated voltage CSA (Use Group C) | 600V |
Rated current CSA (Use Group C) | 10A |
Ex information
Reference hazardous areas | See Downloads – Documentation – Additional Information: Technical Section; Technical explanations |
Ratings per | ATEX: PTB 11 ATEX 1041 U / IECEx: PTB 11.0093U (Ex eb IIC Gb) |
Rated voltage EN (Ex e II) | 350V |
Rated current (Ex e II) | 13A |
Rated current (Ex e II) with jumper | 12A |
Power loss
Power loss, per pole (potential) | 0.434W |
Rated current IN for specified power loss | 13.5A |
Resistance value for specified, current-dependent power loss | 0.002Ω |
Connection data
Total number of connection points | 4 |
Total number of potentials | 2 |
Number of levels | 2 |
Number of jumper slots | 4 |
Connection 1
Connection technology | Push-in CAGE CLAMP® |
Number of connection points | 2 |
Actuation type | Operating tool |
Connectable conductor materials | Copper |
Nominal cross-section | 1 mm² |
Solid conductor | 0.14 … 1.5 mm² / 24 … 16 AWG |
Solid conductor; push-in termination | 0.5 … 1.5 mm² / 20 … 16 AWG |
Fine-stranded conductor | 0.14 … 1.5 mm² / 24 … 16 AWG |
Fine-stranded conductor; with insulated ferrule | 0.14 … 0.75 mm² / 24 … 18 AWG |
Fine-stranded conductor; with ferrule; push-in termination | 0.5 … 0.75 mm² / 20 … 18 AWG |
Note (conductor cross-section) | Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination. |
Strip length | 9 … 11 mm / 0.35 … 0.43 inches |
Wiring direction | Front-entry wiring |
Connection 2
Number of connection points 2 | 2 |
Reviews